GENERAL
UPS Topology: Online Double Conversion
Energy Saving Technology: Online ECO Mode Efficiency > 95%
Active PFC Compatibility: Yes
INPUT
Generator Compatibility: Yes
Nominal Input Voltage (Vac): 200/208/220/230/240
Input Voltage Range (Vac): 180~280
Input Frequency (Hz): 50 ± 10 60 ± 10
Input Frequency Detection: Auto-sensing
Rated Input Current (A): 30
Input Power Factor: 0.99
Backfeed Protection Connector: Yes
Input Connector Type: Hardwire Terminal Block
OUTPUT
Capacity (VA): 6000
Capacity (Watts): 6000
On Battery Waveform: Pure Sine Wave
On Battery Voltage(s) (Vac): 200 ± 2%/208 ± 2%/220 ± 2%/230 ± 2%/240 ± 2%
Output Voltage Setting: Configurable
On Battery Frequency (Hz): 50 ± 0.5% 60 ± 0.5%
Overload Protection: Internal Current Limiting, Circuit Breaker
Outlet(s) – Total: 11
Outlet Type: Hardwire Terminal Block x1/IEC C19 x 2/IEC C13 x8
Outlet(s) - Battery & Surge Protected: 11
Outlet(s) – Critical Load (CL): 6
Outlet(s) – Non –Critical Load (NCL): 5
Typical Transfer Time (ms): 0
BATTERY
Runtime at Half Load (min): 15
Runtime at Full Load (min): 5
Typical Recharge Time (Hours): 4
Start on Battery: Yes
Smart Battery Management (SBM): Yes
User-replaceable: Yes
Hot-swappable: Yes
Battery Type: Sealed Lead-acid
Replacement Battery Pack: RBP0073
RBP Qty (pcs): 2
Battery Qty (Each RBP) (pcs): 10
Battery Voltage (Each RBP) (V): 120
Single Battery Capacity (AH): 12V7AH
Extended Battery Module (EBM): BPE240V30ART3U
Max.EBM Qty: 10